TECHNICAL SPECIFICATIONS

 

NOMINAL VOLTAGES
100 V (100 V – 120 V ± 10%)
200 V (200 V – 240 V ± 10%)
400 V (380 V – 480 V ± 10%)
575 V (500 V – 575 V ± 10%)
690 V (500 V – 690 V ± 10%)
CONTROL MODE
Vector control of induction motors in open loop or V/Hz
Open loop rotor flow control for induction motors (RFC-A)
Open Loop Permanent Magnet Motor Control (RFC-S)

INDIVIDUAL DRIVES: 

SIZE DIMENSIONS (H X W X D) WEIGHT KG (LB)
mm
pulg.
kg
lb
3
365 x 83 x 200
14.4 x 3,3 x 7,9
4,5 max.
9,9 max.
4
365 x 124 x 200
14.4 x 4,9 x 7,9
6,5
14,3
5
365 x 143 x 200
14.4 x 5,6 x 7,6
7,4
16,3
6
365 x 210 x 227
14.4 x 8,3 x 8,9
14
30,9
7
508 x 270 x 280
20 x 10,6 x 11
28
61,7
8
753 x 310 x 290
29.7 x 12,2 x 11,4
52
114,6
9A
1049 x 310 x 290
41.3 x 12,2 x 11,4
66,5
146,6
9E(*)
1010 x 310 x 290
41.3 x 12,2 x 11,4
46
101,4
10E(*)
1010 x 310 x 290
41.3 x 12,2 x 11,4
46
101,4

† Internal line inductance not included

MODULAR DRIVES:  

SIZE DIMENSIONS (H X W X D)
Mm
pulg.
ACTION
9D(*)
773 x 310 x 290
30,4 x 12,2 x 11,4
10D(*)
773 x 310 x 290
30,4 x 12,2 x 11,4
RECTIFIER
10D(*)
6 pulses
355 x 310 x 290
6 pulses
15,8 x 12,2 x 11,4

CHARACTERISTICS

Flexible functionality that minimizes resource usage

  • Offers flexibility in cabinet mounting options, I/O and fieldbus communications.
  • The F300 is a flexible solution for panel mounting, system integration and wall mounting in clean environments.
  • Our Automation Centers are able to provide tailor-made solutions according to customer specifications.
  • It has extensive integrated programming capability for applications with fans, pumps and compressors.
  • The Onboard PLC provides extensive programming functionality compatible with IEC 61131-3 at no additional cost.
  • Optimal energy efficiency.
  • Maximum efficiency in its class through optimized combinations of motor and drive.
  • Enables compliance with the latest CE efficiency standards with induction AC motor control and Ultra Efficient IE4 PM/Super Nema Premium motors.

Ease and speed in the design, construction and commissioning phases

  • The small dimensions of the drive make installation easier and more economical.
  • The drive’s programming software allows quick and easy code development, while the dialogue interface and PC tools facilitate quick and convenient commissioning, diagnostics and maintenance.
  • It has a wide variety of motor control functions with quick access to meet the demands of fluid control in ventilation, pumping and compression applications.
  • The wide range of I/Os increases component connectivity.
  • The drive supports multiple fieldbus protocols.
  • Wide power range from 1.1 kW to 2.8 MW to match the nominal capacity of your fans, pumps and compressors.
  • PC tools allow you to set specific macros for pumps and fans ensuring quick and easy process optimisation.
  • Two PID controllers, with anti-windup and user-scaled, offer specific functionality for fluid control.
  • Logic functions such as ‘AND’, ‘OR’, ‘invert’, ‘binary sum’ and ‘timer’ can be used through simple parameter settings.
  • Real-time clock available on the KI-HOA RTC keyboard as standard.
  • Water hammer control with S-ramp acceleration.
  • Motor detection in rotation
  • Fire detection mode that allows the passage to failure in case of fire for the extraction of smoke.
  • Low load monitoring and hysteresis management for detection of broken belt and dry pump.

Flexible I/O range

Specific I/Os for pumping, venting and compression applications.
2 analog inputs, 2 analog outputs, 3 digital inputs.
3 configurable digital inputs/outputs, 2 switched relay outputs.
1 Safe Torque Off input

Safe Torque Off

Safe Torque Off functionality eliminates the need for a contactor and the obligation of complete shutdown for safe access to machinery.

High degree of compliance with low harmonics

Low harmonic emissions and high degree of conformity.

OPTIONS

Keyboards

Teclado KI-HOA RTC
The KI-HOA RTC keypad allows manual-off-automatic control. The display features up to four lines of real text with multilingual translation for increased clarity and ease of use. A battery-powered real time clock allows date and time to be added to diagnostics and facilitates quick troubleshooting.
Remote keyboard
All features of the CI-Keypad LCD but with remote mounting. This allows flexible mounting on the outside of a panel and complies with IP66 (NEMA 4).

System integration modules – Communications

SI-PROFIBUS
PROFIBUS-DP (Decentralized Peripheral) interface module for connecting slave units. It is possible to use more than one SI-PROFIBUS or a combination of SI-PROFIBUS and other option modules to add additional functionality, such as I/O extension, Gateway functionality or additional PLC functions.
SI-DeviceNet
The DeviceNet network system interface enables connectivity to slave units. It is possible to use more than one SI-DeviceNet or a combination of SI-DeviceNet and other option modules to add additional functionality such as I/O extension, Gateway functionality or additional PLC functions.
SI-CANopen
CANopen interface module supporting various profiles and operating modes
SI-Ethernet
External Ethernet module that supports PROFINET RT*, Ethernet/IP and Modbus TCP/IP, and integrates a Web server that can generate e-mail messages. The module is used to enable high-speed drive access, global connectivity and integration with IT network technologies such as wireless networking.
SI-PROFINET RT
The PROFINET RT interface module provides fast, high-precision communications for maximum plant productivity. The two-port cable connection ensures quick and easy installation. PROFINET is an Ethernet-based industrial network protocol that adapts Ethernet hardware to the real-time needs of industrial automation.

System integration modules – additional I/O

SI-I/O
I/O expansion interface module to increase the number of I/O points on the drive. Additional features: 4 digital I/Os, 3 analog inputs (default)/digital inputs, 1 analog output (default)/digital input, 2 relays

Drive interface units – Back-up

Smartcard
The optional Smartcard memory device can be used to back up basic PLC parameter sets and programs and copy them from one drive to another.
SD Card Adaptor
Conversion device that allows an SD card to be inserted into the Smartcard slot to duplicate application parameters and programs.

Drive interface units – Communications 

  Communications cable CT USB

The USB communications cable allows the PC to be connected to the drive and configured with Connect PC Tool. Connect PC Tool is recommended for configuration of LSRPM motors. Drives with an Ethernet port allow connection to a PC via a standard Ethernet cable.

SOFTWARE

Commissioning and control software

Unidrive M Connect – Commissioning tool
Unidrive M Connect, based on 25 years of Control Techniques experience, is our latest drive configuration tool for commissioning, optimization and monitoring of drive/system performance.

Automation and motion programming software


Machine Control Studio
Control Techniques’ Machine Control Studio provides a flexible and intuitive environment for programming the new automation and motion control functions of Unidrive M drives.

REQUEST PRODUCT INFO